[email protected]+86-799-7618678

C4-80 II 10kV Porcelain Post Insulator GOST

C4-80 II GOST post insulator for 10 kV switchgear. 80 kV test voltage, 4 kN breaking force, 300 mm creepage, 100 N.m torsion, 2.75 kg, UKhL1 climatic execution.

Post Insulators production

  • Home
  • Products
  • Post Insulators
  • C4-80 II 10kV Porcelain Post Insulator GOST

Product Overview

A GOST-pattern solid-core post insulator for 10 kV switchgear, used to support the live parts of disconnectors and circuit breakers inside distribution assemblies. Test voltage is 80 kV against a 10 kV rating, minimum breaking force is 4 kN, and a unit weighs 2.75 kg. The ceramic body is group 120 electrotechnical porcelain to GOST 20419-83, with AK12 aluminium alloy or nodular iron fittings.

  • GOST

Why Buyers Choose This Part

  • Built to the GOST material specifications Russian and CIS buyers ask for by clause
  • 80 kV test voltage against a 10 kV rating leaves clear dielectric margin
  • 4 kN cantilever strength with 100 N.m torsion strength for switch operating loads
  • Silicone sealant on the cement joints keeps water out of the armature seam

Where It Is Used

  • 10 kV disconnectors and circuit breakers in distribution switchgear
  • Indoor switchgear assemblies built to GOST and UKhL1 climatic classes
  • Replacement of aged C4-80 II units during switchgear refurbishment
  • Switchgear manufacturers exporting to CIS markets

Who It Suits

  • Switchgear manufacturers building to GOST specifications
  • Utilities in Russia and CIS countries maintaining 10 kV assemblies
  • Distributors supplying GOST-pattern electrical porcelain

What Goes Wrong Without The Right Part

  • Finding a supplier that will hold the GOST material clauses, not just the dimensions
  • Post insulators that loosen at the cement joint after a few switching seasons
  • Torsion failures when the insulator is used as the operating shaft support
  • Long procurement lead times on discontinued GOST part numbers

How It Is Built

  • Rated 10 kV with 80 kV test voltage
  • Minimum mechanical breaking force 4 kN
  • 300 mm creepage distance
  • 100 N.m torsion strength
  • UKhL1 climatic execution
  • 2.75 kg unit weight

Published Figures For This Product

Every value below comes from the manufacturer data for this item. Figures not listed are confirmed against the drawing before an order is placed.

Minimum Mechanical Breaking Force4 kN
Creepage Distance300 mm
Torsion Strength100 N.m
Unit Weight2.75 kg
Cantilever Strength4 kN
Rated Voltage10 kV
Test Voltage80 kV

Materials

  • Group 120 electrotechnical ceramic to GOST 20419-83
  • AK12 aluminium alloy fittings to GOST 1583-93, or nodular iron
  • PTs-500 DON Portland cement bonding to GOST 10178-85
  • Silicone sealant on the cement joint

Process

  • Body extrusion and turning
  • Glazing
  • Firing
  • Cement bonding of fittings
  • Joint sealing
  • Electrical test

Testing

  • Cantilever load proof test to the 4 kN figure
  • 80 kV test voltage applied on routine test
  • Cement joint and sealant inspection before despatch

Certification

  • Material specifications to GOST 20419-83, GOST 1583-93 and GOST 10178-85
  • ISO 9001 quality management system

Customisation Options

  • Aluminium alloy or nodular iron fittings as your specification requires
  • Produced to customer drawings and samples
  • Marking to your part numbering

How It Compares

IEC pattern post insulatorSame job, different dimensional and material standard. Specify the C4-80 II when the switchgear drawing calls out GOST clauses.
Cast resin post insulatorPorcelain keeps its surface in UV and does not creep under sustained cantilever load, which matters where the insulator carries an operating shaft.

Before You Order And After It Arrives

  • Confirm the fitting material, aluminium alloy or nodular iron, before ordering
  • Do not exceed 4 kN cantilever or 100 N.m torsion in service
  • Keep the cement joints dry in storage so the sealant is not disturbed
  • Check the glaze for chips before fitting, a chipped shed shortens the creepage

C4-80 II 10kV Porcelain Post Insulator GOST Questions

Related Products

Post Insulators

IO-10/4 UKhL3 Ceramic Post Insulator For Line Supports

Post Insulators

  • Diameter Body 54 mm
  • Height 272 mm
  • Minimum Puncture Voltage 75 kV

IPU-10/630-7.5 I UKhL1 Wall Bushing With Oval Flange

Post Insulators

  • Rated Current 630 A
  • Minimum Mechanical Bending Failure Load 7.5 kN
  • Rated Voltage 10 kV

J8-125 Post Ceramic Insulator 8kN Bending Strength

Post Insulators

  • BIL 125 kV
  • Bending Strength 8 kN
  • Maximum Shed And Outer Diameter 110 mm

IO-10/4 UKhL3 and IOR-10/3.75 II UKhL2 Post Insulator

  • Body Diameter 54 mm
  • Overall Height 272 mm
  • Minimum Puncture Voltage 75 kV

Related Cases Guides And Applications

How Electrical Porcelain Bushings And Insulators Are Made

Low Voltage Post Insulators Principles Applications And Selection

Overhead Line Contractors

Switchgear Manufacturers

Manufacturing To Your Drawing Or Sample

Quote For C4-80 II 10kV Porcelain Post Insulator GOST

Send the quantity and any drawing you have. Enquiries are answered within 24 hours, and we produce to customer drawings and samples.

Product Photographs

C4-80 II 10kV porcelain post insulator standing uprightC4-80 II post insulator top fitting and thread detailC4-80 II post insulator base flangeC4-80 II post insulator shed profile close upC4-80 II porcelain post insulators grouped togetherC4-80 II post insulator dimensioned drawingIO-10/4 UKhL3 ceramic post insulator on a plain backgroundIPU-10/630-7.5 wall bushing insulator with oval flangeJ8-125 white post ceramic insulator standing uprightIO-10/4 UKhL3 ceramic post insulator standing upright

Related Products

Request a Quote

We reply to every enquiry within one business day. Write to us directly by email or WhatsApp — both reach our sales desk immediately.